Generator Set Automatic Start Control Module DSE 7320
Product description
The 7320 is an automatic utility (mains) fault control module for a variety of single, diesel or gas generator set applications.
Monitoring a large number of engine parameters, the module will display warnings, shutdowns and engine status information on a backlit LCD screen, illuminated LEDs, remote PC and SMS text alerts (using an external modem).
The 7320 will monitor utility (mains) power and includes USB, RS232 and RS485 ports and dedicated terminals for system expansion.
I. Characteristics:
4-line backlit LCD text display
Five-button menu navigation with PIN protection
Front panel editor for LED and LCD alarm indication Customizable status screen
Power saving mode supports up to three remote display units
9 configurable inputs 8 configurable outputs
Flexible transmitter input
II. Benefits:
132 x 64 pixel scale display and clear real-time clock provide accurate event recording
Multiple date and time schedules can be configured to set maintenance intervals to maintain optimal engine performance Ethernet communication (via DSE860/865 modules) provides advanced remote monitoring at low cost Modules can be integrated into Building Management Systems (BMS)
License-free PC software IP65 rating (with included gasket) for increased water resistance through DSENet® for increased input and output scalability
III. Specifications:
DC Power Supply
Continuous voltage rating: 8 V to 35 V continuous
The start-up differential is capable of lasting 50 mS at 0 V, provided that the power supply is at least 10 V before the differential and the power supply returns to 5 V. This is achieved without the need for an internal battery.
LEDs and backlight are not maintained during start-up. 12 mA maximum operating current at 340 V, 24 mA maximum standby current at 160 V, 12 mA at 160 V Charge fault/excitation range 80 V to 24 V
Municipal electricity
Voltage Range
15 V - 333 V AC (L-N)
Frequency range
3.5 Hz 至 75 Hz
Output
15 A DC supply voltage Output B (start-up) 15 A supply voltage DC Outputs C and D 8 A 250 V (no voltage) auxiliary outputs E, F, G, H 2 A DC supply voltage
Voltage Range
15 V - 333 V AC (L-N)
Frequency range 3.5 Hz to 75 Hz
Magnetic pickup voltage range +/- 0.5 V to 70 V
Frequency range
10,000 Hz (maximum)